Arrangement of efficient energy-saving, supply and exhaust, single-room ventilation in flats, houses, cottages, social and commercial premises.Reducing heat losses caused by ventilation due to heat recovery.
Humidity balance and regulated air exchange create individually controlled microclimate.Wi-Fi communication between several single-room ventilation units for coordinated operation.Controlled by Android or iOS smartphone or tablet.
DESIGN
Easy maintenance.Indoor unit is opened by pressing the latches on both sides.
The specially designed front panel can be closed manually to ensure 100% air tightness and protect against wind impact.
One of the best regeneration efficiency on the market due to innovative hexagonal structure of the heat exchanger cells.
Integrated automatic airshutters prevent air backdrafting.
Built-in Wi-Fi for wireless communication between units and Android or iOS device control.
UNIT OPERATING LOGIC IN WINTER PERIOD
Warm stale air is extracted from the premise, flows through the ceramic regenerator and transfers its heat energy and moisture to it.As the ceramic regenerator gets warmed up, the unit switches to the supply mode.
Clean cold intake air flows through the regenerator and absorbs accumulated heat and humidity.When the ceramic regenerator is cooled down, the unit switches to the extract air mode.
CONTROL
The units can be connected by Wi-Fi for synchronized operation.
The units can be connected by Wi-Fi. Northvent PRO app for Android or iOSdevices is available at Google Play and AppStore.
MOUNTING
The unit is designed for through-the-wall installation inside a prepared hole in an outer wall of the building.The best ventilation solution is pairwise installation of reverse phase connected units. Some units ensure supply of fresh air to the room and the other units extract air from the premise. This way the most efficient balanced ventilation is arranged.
In case of brand new construction, units are mounted in two stages:
Pre-installation of an air duct and an outer ventilation hood at the stage of indoor finishing and outer decorative wall finishing.
Completion of the installation before commissioning of a house. It includes installation of the indoor unit with controller and shutters, the cartridge, the regenerator, the fan and the filters.
Angular mounting into a wall with standard thickness using KIT BlauPlast white 160 / KIT BlauPlast chrome 160
Characteristics
Parameter
Expert A50-1 W (1 speed)
Expert A50-1 W (2 speed)
Expert A50-1 W (3 speed)
Measurement unit
Voltage
100-230
100-230
100-230
V
Frequency
50/60
50/60
50/60
Hz
Power
4.45
5.08
7.06
W
Current
0.035
0.04
0.059
A
RPM
800
1300
1900
min-1
Air flow in ventilation mode
4
8
14
l/s
Air flow in ventilation mode
15
30
50
m³/h
Air flow in heat recovery mode
2
4
7
l/s
Air flow in heat recovery mode
8
15
25
m³/h
Sound pressure level at 1 m
20
27
30
dBА
Sound pressure level at 3 m
11
18
21
dBА
Temperature of transported air
-20…+50
-20…+50
-20…+50
°С
Ingress protection rating
IP24
IP24
IP24
–
Filter
G3 (F8 PM2,5 > 99 %)
G3 (F8 PM2.5 > 99 %)
G3 (F8 PM2.5 > 99 %)
–
Regeneration efficiency in accordance with DIBt LÜ-A 20
≤ 93
≤ 93
≤ 93
%
Outdoor sound pressure attenuation in accordance with DIN EN 20140
42
42
42
dBА
SEC class
A
A
A
–
Mounting
wall mounting
wall mounting
wall mounting
–